Receptacles: Bootleg Grounds

 

Ungrounded power outlet receptacle

Dated 2-prong ungrounded receptacle

 

All about bootleg grounds

The outlets in our homes are a necessary component of modern living.  Our culture is dependent on readily available access to power.  Ever since we harnessed electricity, we have witnessed the ongoing evolution for safety.  Safety, it would seem, does come without a price.  And bootleg grounds, unfortunately, are one way of avoiding that expense.

Part of the issue that comes with owning an older home is that the three-prong cords on electrical devices will not jive with older pre-1960 two-slot receptacles.  To begin with, one way to deal with this is to use an “adapter” similar to the one pictured below.   This device lets you connect your three-pronged appliances into older two-slot receptacle outlets.  So what’s the problem?  The problem is you have effectively cut out the safety mechanism the grounded electrical system provides along that third prong. 

Ungrounded plug adapter

Grounded to ungrounded plug adapter

Replacing an older two-slot receptacle with a three-slot model does not, by itself, provide an equipment-grounding path. Newly installed outlets and cover plates can conceal older wiring, so appearance alone is not a reliable guide to electrical safety.

What should they do? 

NEMA 5-15R

Modern 3-prong grounded receptacle

A qualified electrician should determine suitable replacement and grounding arrangements for the existing wiring. A three-slot receptacle alone does not establish that an effective equipment ground is present. Basic plug-in testers also have limits: the Klein RT100 documentation, for example, says it does not indicate ground quality, some combinations of defects, or reversal of grounded and grounding conductors. A reassuring light pattern is not a complete wiring evaluation.

Basic three-light receptacle tester

Basic three-light receptacle tester

Why can a bootleg ground fool a tester?

An improper neutral-to-ground connection at a receptacle can make a basic three-light tester display an apparently normal pattern. Its lights indicate voltage conditions, not a resistance measurement that proves an effective equipment ground. A normal-looking result is not proof that the receptacle is safely grounded. Suspected grounding defects require evaluation by a qualified electrician.

Bootleg grounds

The blue wire is the bootleg jumping the ground to the neutral terminal.  This is an illegal configuration.

Recently changed receptacles in an older home can prompt questions about the underlying wiring. Age and appearance are clues for further evaluation, not proof of a particular defect.

What do we do then? 

Inspection observations and test readings may indicate a need for further evaluation. They do not guarantee discovery of concealed wiring defects. A qualified electrician should evaluate suspected grounding problems and determine the appropriate correction. Receptacle removal is not promised as part of every home inspection.

What’s the bottom line? 

A bootleg ground improperly connects the equipment-grounding contact to the current-carrying neutral at the receptacle. This can create a serious shock hazard, particularly when other wiring faults are present. It does not mean every connected appliance frame is always at the same hazardous voltage; the danger depends on the circuit conditions. A qualified electrician should evaluate and correct the defect.

If you suspect a wiring problem, contact a qualified electrician. Do not remove receptacles or attempt internal wiring checks yourself. A home inspection can document accessible conditions and recommend follow-up, but does not replace electrical diagnosis or repairs.

Contact Realm to discuss a home inspection.